SIEMENS 5WG1141-1AB21 KNX / DALI Gateway twin plus N141 / 21

SKU: 5WG1141-1AB21 Category: Tag:

5WG1141-1AB21

Description

With emergency lighting, with sensors
For communication via KNX EIB with electronic ballasts (ECG) with a DALI interface
Two DALI outputs with DALI-2 certification acc. to IEC 62386-101 and 103, each for communication with up to 64 DALI ECG Ed.1 and DALI-2 and at least 10 sensors
Integrated power supply with input voltage AC 110-240 V, 50-60 Hz or DC 120-240 V for powering the gateway electronics and DALI output
Maximum DALI output voltage of 19 V, short circuit resistant
Incorrect voltage detection during commissioning if incorrect power line is connected to a DALI output
LED display for displaying operation mode and error messages
Pushbutton for switching between bus and direct operating mode
One pair of pushbuttons for switching On/Off of all connected DALI ECG
One LED per DALI output for status signal of all connected luminaries in direct mode
Configurable assignment of max. 64 DALI ECG per channel to max. 16 DALI groups per channel, exclusive controlled in groups or single (switching, dimming, set dimming value and color temperature) and feedback for group status and lamp failure
Support of DALI DT8 ECGs for colour temperature control (Tunable White). Individual, group, scene, effect and schedule control for Human Centric Lighting
Configurable behaviour for bus failure (stand-alone mode)
Configurable pre-loaded applications without software ETS
Configurable function burn-in for all ECG via pushbutton or single via object
Scheduler for day, week, date with astro function
Control of all connected luminaries together in broadcast mode
Status signal and display of lamp and ECG failure per group and per DALI device
Transformation of dimming commands into a temporary setpoint adjustment for ECG with integrated constant light level control and directly connected light level sensor
One or two level timer
Up to 4 integrated one time or cyclical control of repeatable sequences or color effects
Distinction between self-contained emergency luminaries with one or two DALI devices
Starting the self-conducted testing of each individual inverter and reporting the test result via bus or save in a persistent memory with memory space monitoring over object
Distinction between function test, short duration test, and long duration test
Optional configuration of any DALI ECG to dim to a preset dimming value in of emergency mode
Locking of switching and dimming commands as well as configuration while emergency mode is activated
Activation of emergency mode based on a configurable number of failed DALI ECG
Lock object to elimination of failure messages interruption of ECG during emergency lighting testing
Inhibit mode for disabling battery mode of self-contained emergency luminaries over pushbutton
Per channel up to 6 stand-by-area analysis for activation of switch actuators
Scene control for up to 16 scenes per channel
16 integrated 2-level-controller for brightness control and 16 constant light level controller for main luminaries group and up to 4 additional luminaries groups
Assignment of a CIN to a DALI ECG
Reintegration defective DALI ECG without ETS
Assignment of DALI ECG to groups and test option for ECG, groups, scenes and effects via ETS
Assignment of DALI sensors and test option of sensors via ETS
Integrated bus coupling unit with only half a standard bus load, bus connection via bus terminal
Mounting on DIN rail EN 60715-TH35-7.5